Portable gas analyzer using electrochemical gas sensors.
|
|
| Description GA-21plus |
|
|
|
|
 |
The madur 21plus portable flue gas analyzer utilizes the latest available technology for measuring and controlling combustion gas parameters in boilers, burners, industrial engines, and other fuel-burning combustion systems.
Two different models are available that provide standard measurement features, as well as advanced sample conditioning capabilities when EPA precompliance or compliance methods are required. Each is compact, easy to operate, and complete with all the necessary functions for maintaining a proper combustion management program. This portable flue gas analyzer is small enough to qualify as hand baggage on the airlines and fit under the seat!
Both models of this flue gas analyzer can be found around the world wherever fuel is burned, working to keep our environment clean and fuel costs down.
|
|
| GA-21plus in soft case |
|
|
|
|
|
| The GA-21plus is a unique, extremely lightweight, but robust, instrument designed to assist burner and engine operators in field maintenance of industrial combustion systems. The instrument is a four or five gas analyzer providing semicontinuous measurements of O2, CO, stack temperature, draft, NO, NO2, SO2, or CxHy. Calculations include CO2, combustion efficiency, NOx, excess air and stack losses. A high-quality pump pulls a sample through the supplied 10 foot sample line and probe into the analyzer through an inline water trap and filter.
A reservoir collects the gases where they are then “pushed” to the temperature compensated sensors at a controlled flow rate allowing for extremely accurate gas analysis for each channel. A large full-line display shows all measured and calculated parameters simultaneously for easy viewing, while an integral dot matrix impact printer provides hard copy of all parameters at the push of a button.
This is the portable flue gas analyzer of choice in many industries, used for general maintenance as well as EPA compliance testing. This is a workhorse, no laboratory instrument, despite its accuracy. Precompliance testing and general tuning of burners, all in one package!
|
 |
|
|
GA-21plus in hard case |
|
|
|
Back to GA21plus |
|
| Features GA-21plus |
|
|
|
- Highly accurate electrochemical analysis
- Backlit digital display with zoom
- Easily transportable lightweight design
- Graphics for 5 minute hysteresis can be displayed and printed
- RS232C interface to computer
- CO fresh air bypass avoids sensor saturation
- Temperature compensated cells
- Optional probe and cable lengths available
- Optional gas preparation system
- Infrared sensors for methane (CH4) and carbon dioxide (CO2) available
|
|
| Applications GA-21plus |
|
|
|
- Boiler flue gas analysis
- Engine emission testing
- Burner management
- Precompliance and compliance level testing
- Title V permitting
- Meets SCAQMD requirements includes automatic O2 correction
- Landfill measurements with the optional infrared sensors for methane and carbon dioxide.
- Environmental reporting capabilities Peltier cooler, heated sample line, heated probe and filter. Other portable flue gas analyzers also available upon request. Please contact us for more information.
|
|
|
Back to GA21plus |
|
| Measurements data GA-21plus |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Parameter |
Measuring method
|
Range |
Resolution |
Accuracy |
Detection
Limit |
Time (T90) |
|
| Gases measured in standard configuration |
O2 - oxygen,
volumetric concentration |
electrochemical gas sensor |
0..25 % |
0.01 % |
±0.2 % or 2 % rel. |
0.01 % |
45 s |
CO2 - carbon dioxide,
volumetric concentration |
calculated from volumetric concentration of O2 |
0..25 % |
0.01 % |
±0.2 % or 2 % rel. |
0.01% |
45 s |
CO - ambient carbon monoxide,
volumetric concentration |
electrochemical gas sensor |
0..100 ppm
|
0.1 ppm
|
±5 ppm or
5 % rel.
|
1 ppm
|
45 s
|
CO - carbon monoxide,
volumetric concentration |
electrochemical gas sensor |
0..20000 ppm
|
1 ppm
|
±5 ppm or
5 % rel.
|
5 ppm
|
45 s
|
COmg - carbon monoxide,
mass concentration |
calculated from volumetric concentration of CO |
0...
|
1 mg/Nm3
|
±10 mg/Nm3
or 5 % rel.
|
10 mg/Nm3
|
45 s
|
COrel - carbon monoxide,
mass concentration relative to O2 |
calculated from volumetric concentration of CO and O2 |
0...
|
1 mg/Nm3
|
±10 mg/Nm3
or 5 % rel.
|
10 mg/Nm3
|
45 s
|
| Gases measured with optional IR sensors |
CO2 - carbon dioxides,
volumetric concentration |
IR sensor |
0..5 % 0...1000 %
|
0.01 %
0.1 %
|
0.20 %
|
0.20 %
|
45 s
|
CH4 - Methane,
volumetric concentration |
IR sensor |
0...5 % 0...100 %
|
0.01 % 0.1 %
|
0.20 %
|
0.20 %
|
45 s
|
| Gases measured with optional electrochemical sensors |
| NO - volumetric concentration of nitric oxide. |
electrochemical gas sensor |
0..1000 ppm
|
1 ppm
|
±5 ppm or
5 % rel.
|
5 ppm
|
45 s
|
| NOmg - mass concentration of nitric oxide. |
calculated from volumetric concentration of NO |
0...
|
1 mg/Nm3
|
±15 mg/Nm3
or 5 % rel.
|
15 mg/Nm3
|
45 s
|
| NOrel - mass concentration of nitrogen oxides relative to O2 |
calculated from volumetric concentration of NO and O2 |
0...
|
1 mg/Nm3
|
±15 mg/Nm3
or 5 % rel.
|
15 mg/Nm3
|
45 s
|
| NO2 - volumetric concentration of nitrogen dioxide. |
electrochemical gas sensor |
0..1000 ppm
|
1 ppm
|
±5 ppm or
5 % rel.
|
5 ppm
|
45 s
|
| NO2mg - mass concentration of nitrogen dioxide. |
calculated from volumetric concentration of NO2 |
0...
|
1 mg/Nm3
|
±15 mg/Nm3
or 5 % rel.
|
15 mg/Nm3
|
45 s
|
| NO2rel - mass concentration of nitrogen dioxide relative to O2 |
calculated from volumetric concentration of NO2 and O2 |
0...
|
1 mg/Nm3
|
±15 mg/Nm3
or 5 % rel.
|
15 mg/Nm3
|
45 s
|
| SO2 - volumetric concentration of sulfur dioxide. |
electrochemical gas sensor |
0..5000 ppm
|
1 ppm
|
±5 ppm or
5 % rel.
|
5 ppm
|
45 s
|
| SO2mg - mass concentration of sulfur dioxide. |
calculated from volumetric concentration of SO2 |
0...
|
1 mg/Nm3
|
±15 mg/Nm3
or 5 % rel.
|
15 mg/Nm3
|
45 s
|
| SO2rel - mass concentration of sulfur dioxide relative to O2 |
calculated from volumetric concentration of SO2 and O2 |
0...
|
1 mg/Nm3
|
±15 mg/Nm3
or 5 % rel.
|
15 mg/Nm3
|
45 s
|
| Temperature measurements |
| Tgas - flue gas temperature |
Thermocouple |
-10..1000°C
|
1°C
|
±2 °C
or 1.5 % rel.
|
1 °C
|
30 s
|
| Tamb - ambient temperature |
Thermistor |
-10..100°C
|
1°C
|
±1 °C
|
1 °C
|
30 s
|
| T1 - external input |
Thermocouple |
0...1600°C
|
1°C
|
±2 °C
or 1. 5 % rel.
|
1 °C
|
10 s
|
| T2 - external input |
Thermistor |
-20...1000°C
|
1°C
|
±2 °C
or 1. 5 % rel.
|
1 °C
|
10 s
|
| Other measured values |
| U/I - external input |
ADC |
-20...+20 V -20...+20 mA
|
0.01 V 0.01 mA
|
±0.02 V ±0.02 mA
|
0.01 V 0.01 mA
|
10 s
|
| Pressure |
DMS bridge |
-25 hPa ... +25 hPa
|
0.1 Pa
|
± 2 Pa
or 5 % rel.
|
1 Pa
|
10 s
|
| Flow velocity (Option) |
Pitot tube |
1...50 m/s
|
0.1 m/s
|
0.3 m/s or 5 % rel.
|
0.1 m/s
|
10 s
|
| Soot/smoke test |
Bacharach method |
0..9
|
0.5
|
0.5
|
0.5
|
|
| Calculated parameters |
| TI (CO/CO2-Toxic Index) |
calculated |
0...0.01 |
0.0001 |
5 % rel. |
0 |
10 s |
| Lambda - excess air number |
calculated |
1..10 |
0.01 |
2 % rel. |
0 |
10 s |
| qA - combustion losses |
calculated |
0..100 % |
0.1 % |
2 % rel. |
0 % |
10 s |
| Eta - efficiency |
calculated |
0..120 % |
0.1 % |
2 % rel. |
0 % |
10 s |